- Capacity: 6000 VA / 6000 W
- High Density: 2U Size
- Power Factor (PF): 1
- Topology: Double-conversion
- Waveform: Sine Wave
- Output: 200, 208, 220, 230, 240 VAC User Configurable ±2%
- Plug type & cord: Hardwire with NEMA L6-30P Power Cord Option
- Outlet types: 2 × NEMA L6-20R, 2 x NEMA L6-30R
- Communication ports: USB, Serial, SNMP, EPO
- Management software: PowerPanel® Business Edition
- Energy saving: ECO Mode Efficiency >96%
- Warranty: 3 year
| General | |
| Energy Saving | Yes – ECO Mode Efficiency >96% | 
| Energy Star Certified | Yes | 
| UPS Topology | Double Conversion | 
| Battery | |
| Battery Equalization Technology | Yes | 
| Battery Quantity | 12 | 
| Battery Size | 12V/6Ah | 
| Battery Type | Sealed lead acid | 
| Extended Battery Module Option | BP144VL2U01 | 
| Hot Swappable | Yes | 
| Replacement Battery | (1) RB1260X12 | 
| Runtime at Full Load (min) | 1.4 | 
| Runtime at Half Load (min) | 4.9 | 
| Smart Battery Management (SBM) Mode | Yes | 
| Typical Recharge Time | 4 Hours (0-90%) | 
| User Replaceable | Yes – Qualified Personnel Only | 
| Dimensions | |
| Physical Dimensions – (WxHxD) (cm) | 43.18 x 8.64 x 71.88 (cm) | 
| Physical Dimensions – (WxHxD) (in) | 17 x 3.4 x 28.3 (in) | 
| Physical Dimensions – (WxHxD) (mm) | 432 x 86 x 719 (mm) | 
| Weight (kg) | 41.91 | 
| Weight (lb) | 92.4 | 
| Dimensions – Shipping | |
| Shipping – Weight (kg) | 51.98 | 
| Shipping – Weight (lb) | 114.6 | 
| Shipping Dimensions – (WxHxD) (cm) | 59.94 x 21.59 x 109.98 (cm) | 
| Shipping Dimensions – (WxHxD) (in) | 23.6 x 8.5 x 43.3 (in) | 
| Shipping Dimensions – (WxHxD) (mm) | 599.44 x 215.9 x 1099.82 (mm) | 
| Input | |
| Backfeed Protection | Yes | 
| Cold Start | Yes | 
| Cord Length (ft) | 10 | 
| Cord Length (m) | 3 | 
| Input Frequency Range | 40Hz-70Hz (auto-sensing) | 
| Input Power Factor | 0.99 | 
| Input Voltage | 200-240VAC | 
| Input Voltage Range | 120-139VAC for 0-25% Load 140-159VAC for 0-50% Load 160-179VAC for 0-75% Load 180-280VAC for 0-100% Load | 
| Plug Type | Hardwire with NEMA L6-30P Power Cord Option | 
| Output | |
| Bypass | Internal Bypass (Automatic and Manual) | 
| Crest Factor | 3:1 | 
| ECO Mode Bypass Voltage Range | ±10%, ±15% (Configurable) | 
| Harmonic Distortion | THD < 3% at Linear Load, < 5% at Non-linear Load | 
| On Battery Frequency | 50/60Hz (Auto-Sensing or Configurable) ±0.25Hz | 
| On Battery Voltage | 200, 208, 220, 230, 240Vac (Configurable) ±2% | 
| On Battery Waveform | Sine wave | 
| Outlet Type | (2) NEMA L6-20R, (2) NEMA L6-30R | 
| Outlets – Total | 4 | 
| Overload Protection | Line Mode: 105~125% Load for 1 min 126~150% Load for 10 sec Battery Mode: 105~130% Load for 10 sec 131~150% Load for 2 sec | 
| Rated Power Factor | 1 | 
| Short Circuit Protection | UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection | 
| Transfer Time | 0ms | 
| VA | 6,000 (6 kVA) →w/ Hardwire Terminal 5,400 (5.4 kVA) – 240VAC →w/ Power cord 5,400 (5.4 kVA) – 230VAC →w/ Power cord 5,100 (5.1 kVA) – 220VAC →w/ Power cord 4,850 (4.85 kVA) – 208VAC →w/ Power cord 4,500 (4.5 kVA) – 200VAC →w/ Power cord | 
| Watts | 6,000 (6 kW) →w/ Hardwire Terminal 5,400 (5.4 kW) – 240VAC →w/ Power cord 5,400 (5.4 kW) – 230VAC →w/ Power cord 5,100 (5.1 kW) – 220VAC →w/ Power cord 4,850 (4.85 kW) – 208VAC →w/ Power cord 4,500 (4.5 kW) – 200VAC →w/ Power cord | 
| Surge Protection & Filtering | |
| EMI/RFI Filtration | Yes | 
| Surge Suppression | 2430 Joules, per IEC 61000-4-5 Level 3 | 
| Management & Communications | |
| Audible Alarms | Battery Mode, Battery Low, Overload, UPS Fault | 
| Auto Rotatable LCD Control Panel Option | Yes | 
| Dry Contacts | No | 
| Emergency Power Off (EPO) Port | Yes | 
| HID Compliant USB Port | Yes | 
| LCD Control Panel | Multi-Function Color TFT-LCD Readout that Supports: (15) Types of UPS status, (7) Types of Controls, (20) Types of Set Up, (12) Event Logs, (11) Types of About, (4) Types of Diagnostics | 
| LED Indicators | Power On (White) | 
| Management Cable | USB cable, Serial cable | 
| Removable LCD Control Panel Option | No | 
| SNMP / HTTP Remote Monitoring | Yes – RMCARD205 pre-installed | 
| Serial Port | Yes | 
| Software | PowerPanel Business Edition | 
| Physical | |
| Enclosure Construction | Steel | 
| Form Factor | Rack / Tower Convertible (Rotatable LCD) | 
| Mounting Hardware Included | Yes | 
| Rack Height | 2U | 
| Environmental | |
| Audible noise at 1m from surface of unit | 43 dBA to 66 dBA (0% to 100% load) | 
| Operating Elevation | 0-10000 feet (0-3000 meters) | 
| Operating Relative Humidity | 0% – 90% non condensing | 
| Operating Temperature | 32°F to 104°F (0°C to 40°C) | 
| Storage Elevation | 0-50000 feet (0-15000 meters) | 
| Storage Relative Humidity | 0% – 95% non condensing | 
| Storage Temperature | -4°F to 113 °F (-20°C to 45 °C) | 
| UPS Online Thermal Dissipation (100% load) | 1613 BTU/hr | 
| Certifications | |
| Environmental | RoHS Compliant | 
| Safety | UL 1778 5th Ed. CSA C22.2 NO.107.3-05 FCC Part 15 Class A | 
| Warranty | |
| Connected Equipment Guarantee | Lifetime | 
| Extended 2-Year Warranty | Optional WEXT5YR-U20B | 
| Product Warranty | 3 Years Limited | 
 
                                                         
                                                         
                                                         
                                                         
                                                     
                                                     
                                                    